Technical Attributes

General Information
Brand ETHERLINE®
Product type Ethernet cable
valid fieldbus or Ethernet system ETHERNET/IP, PROFINET, Ethernet
Copper index 48.000  kg/km
Copper index (lb) 322.500  lb
Weight 87 kg/km
Electrical Characteristics
Maximum operating voltage (not for power transmission) 125
Nominal surge impedance 100
Nominal voltage 48 V AC rms according to IEC
Supports Power over Ethernet IEEE 802.3af (PoE), IEEE 802.3at (PoE+), IEEE 802.3bt (4PPoE)
Loop resistance at 20°C 143.8
Possible data transmission rates 10000
Test voltage core/screening 1
Test voltage core/core 1
Rated voltage core to core 50 V AC rms according to IEC
Product Design
Nominal core diameter 1.5
Conductor design 7-wire
Nominal outer diameter 8.8  mm
Conductor material Tin-plated copper
Min. outer diameter 8.6
Nominal conductor cross-section (metric) 0.25  mm²
Conductor count/size 4X2X23/7AWG
Optical degree of coverage of the stranded screening, overall screen 85
Shielded

Core identification Colours
Shape of cable Round
Number of pairs 4
Outer sheath colour green
Stranding type Twisted-pair
Pair screening type Aluminium-laminated plastic foil
Leading conductor cross-section AWG
Abbreviation shielding S/FTP
Cable sheath RAL colour RAL 6018
With rodent protection

Conductor colour code PROFINET Colour code 4-pair
Type of overall screen Aluminium-laminated plastic foil, Tin-plated copper braiding
Number of cores 8
Nominal conductor cross-section (AWG) 23 AWG
Core insulation basic material Polyethylene foam
Basic material of outer sheath Halogen-free compound
Including protective earth

Core insulation basic material, short form Foam-Skin PE
Max. outer diameter 9
Number of wires 7
Product Characteristics
Flame-retardant

PWIS-free according to VDMA 24364-B2-L
Halogen-free according to VDE 0472-815
For continuous flexing

Fast Connect (FC) cable

PROFINET® application Type B
Installation temperature min. -20
UV-resistant

Minimum bending radius in mm, fixed installation 72.0  mm
PWIS-free

Application area Flexible
max. conductor temperature, occasionally moved -20 °C to 60 °C max. conductor temperature:
Oil-resistant

Ethernet cable category Cat.6A
Minimum bending radius in mm, occasionally flexing 135.0  mm
Max. assembly temperature 60
Minimum bending radius, stationary 8 x outer diameter
Minimum bending radius, occasionally flexing 15 x outer diameter
Temperature, fixed installation -40 °C to 80 °C max. conductor temperature:
Flame retardance according to UL VW-1
UV-resistant according to UL sunlight resistant
Windable

Halogenfree

Certifications and Standards
DNV-certified

cUR recognized

CSA certified

TÜV certified

UL certification UL CM according to UL 444 (e-file number: E236660)
Ecolab certified

cUL listed

UL listed

CE marked

cUL certification cUL CM (75°C) according to CSA C22.2 No. 214 (e-file number: E236660)
UL recognized

VDE certified

EAC certification number ЕАЭС N RU Д-DE.АЮ64.В.00130/20
EAC-certified

Documentation
Notes
  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.
  • Unless specified otherwise, the product values shown are rated values at room temperature. You can receive further values, such as tolerances, upon request if they are available and have been released for publication.
Product Family List
All articles from ETHERLINE® PN FLEX Cat.6A
Article number Conductor count/size Copper index calc export Imp outer dia cable sheath nom Nominal outer diameter Weight
2170930 4X2X23/7AWG 8.8 92 kg/km
2170931 4X2X23/7AWG 8.8 87 kg/km